Availability Availability calculations are made on definitions that are generic, transparent, unambiguous and based on realistic measurements. All turbine time is recorded and assigned to fifteen mutually exclusive categories as shown in the table below. The availability may be calculated over any time period.
Default calculations are supplied with the system. In addition the user may define their own availability calculations based on the addition and division of these time categories.
| Availability category |
Time |
Status |
| No SCADA |
T1 |
The SCADA system is out of operation. |
| Force majeure |
T2 |
Force Majeure condition exists on the wind farm. |
| No comms |
T3 |
The SCADA communications system is functioning correctly but no data
communication is available from the turbine controller. |
| On line |
T4 |
Turbine generator on line. |
| Grid limits stop |
T5 |
The grid is outside agreed operational limits. |
| Ambient temperature stop |
T6 |
The wind farm ambient temperature is outside the agreed turbine
operational limits. |
| Off line wind in limits |
T7 |
Turbine is released to run and wind is within limits but turbine generator
is off line. This may be due to turbine operations such as cable unwinds
and generator changes. |
| Off line wind out limits |
T8 |
Turbine is released to run but generator is off line due to wind conditions
being outside the operational limits. |
| Fault stop wind in limits |
T9 |
Turbine is stopped with a turbine fault requiring operator intervention.
Wind is within operational limits. |
| Fault stop wind out limits |
T10 |
Turbine is stopped with a turbine fault requiring operator intervention.
Wind is outside operational limits. |
| Maintenance stop wind out limits |
T12 |
Turbine is stopped for scheduled or unscheduled maintenance while the
wind is outside operational limits. |
| Operator stop wind in limits |
T13 |
Turbine is stopped by operator command while the wind is within
operational limits. |
| Operator stop wind out limits |
T14 |
Turbine is stopped by operator command while the wind is outside
operational limits. |
| Constraint stop |
T15 |
Turbine is stopped for operational constraints (time of day, noise etc).
May be manual or pre-programmed. |
|
|