Availability

Availability calculations are made on definitions that are generic, transparent, unambiguous and based on realistic measurements. All turbine time is recorded and assigned to fifteen mutually exclusive categories as shown in the table below. The availability may be calculated over any time period.

Default calculations are supplied with the system. In addition the user may define their own availability calculations based on the addition and division of these time categories.

Availability category Time Status
No SCADA T1 The SCADA system is out of operation.
Force majeure T2 Force Majeure condition exists on the wind farm.
No comms T3 The SCADA communications system is functioning correctly but no data communication is available from the turbine controller.
On line T4 Turbine generator on line.
Grid limits stop T5 The grid is outside agreed operational limits.
Ambient temperature stop T6 The wind farm ambient temperature is outside the agreed turbine operational limits.
Off line wind in limits T7 Turbine is released to run and wind is within limits but turbine generator is off line. This may be due to turbine operations such as cable unwinds and generator changes.
Off line wind out limits T8 Turbine is released to run but generator is off line due to wind conditions being outside the operational limits.
Fault stop wind in limits T9 Turbine is stopped with a turbine fault requiring operator intervention. Wind is within operational limits.
Fault stop wind out limits T10 Turbine is stopped with a turbine fault requiring operator intervention. Wind is outside operational limits.
Maintenance stop wind out limits T12 Turbine is stopped for scheduled or unscheduled maintenance while the wind is outside operational limits.
Operator stop wind in limits T13 Turbine is stopped by operator command while the wind is within operational limits.
Operator stop wind out limits T14 Turbine is stopped by operator command while the wind is outside operational limits.
Constraint stop T15 Turbine is stopped for operational constraints (time of day, noise etc). May be manual or pre-programmed.